• Low Pour point. • High dielectric strength. • Non corrosive as tested by all present methods, DIN & ASTM tests & New IEC 62535 method. • Low viscosity oils offering excellent and fast heat transfer. • Compatible with transformer construction material.
Eiffel Elect Oil-U Class-I Un-inhibited Transformer oil is highly suitable for all grades of
• Power Transformers, Distribution Transformers
• Circuit Breakers, Oil filled switches, X-ray equipment
Specifications
Eiffel Elect Oil-U Class-I Un-inhibited Transformer oil meets or exceeds following International and Builder specifications:
Typical Characteristics
| TEST DESCRIPTION | TEST METHOD | SPECIFICATION LIMITS |
|---|---|---|
| Function | ||
| Kinematic Viscosity, mm2/s(Max) | ISO 3104 | |
| at 40 0C | 12.0 | |
| at -30 0C | 1800 | |
| Pour Point | ISO 3016 | < -40 |
| Woter Content, Max mg/kg | IEC 60814 | |
| a) Bulk | 30 | |
| b) Drum | 40 | |
| Break Down Voltage, Min | IEC 60156 | |
| a) As Delivered (Kv) | 30 | |
| b) After Treatment (Kv) | 70 | |
| Density kg/dm3, @20 0c, Max | ISO 3675 | 0.895 |
| DDF at 90 0c, Max | IEC 60247 | 0.005 |
| Refining/Stability | ||
| Appearance | Visuval | Clear, odourless, liquid free from suspend impurities |
| Neutralization Value / Acidity, mg KOH/g, Max | IEC 62021-1 / IEC 62021-2 | 0.01 |
| Interfacial tension, mN/m, Min | ISO 6295 | 40 |
| Total sulphaur Content %, Max | IP 373/ ISO 14596 | No General Requirment |
| Corrosive sulphaur , Silver strip. 100°C, 18hrs | DIN 51353 | Non Corrosive |
| Cu strip & kraft Paper 150°C, 72hrs | IEC 62535 | Non Corrosive |
| Anti-Oxiddant Additives | IEC 60666 | Not detectable |
| 2-Furfural content. mg/kg, Max | IEC 61198 | 0.1 |
| Perfomance | ||
| Oxidation Stability, 164 hrs | IEC 61125 METHOD-C |
|
| – Total acidity. mg KOH/g, Max | 1.2 | |
| – Sludge, %, Max | 0.8 | |
| – DDF @90°C, Max | IEC 60247 | 0.5 |
| Health, safty and environment (HSE) | ||
| Flash Point °C, PMCC , Min | ISO 2719 | 135 |
| Polycyclic Aromatics % mass, Max | IP:346 | 3.00 |
| Total PCB content mg/Kg | IEC 61619 | Not Detectable |
| Conforms to Standards | ||
| ICE 60296:2003(U) | ok | |
| ASTM D 3487 Type I | ok | |
The above figures are typical of blends with normal production tolerance and do not constitute a specification.